Winter Generation Deliverability |
GD-W252, GD-W253, GD-W257, GD-W258
|
ComEd |
574 |
Install two (2) 765 kV circuit breakers at Wilton Center substation and move the Collins line exit to a new bus position |
Summer N-1 & N-1-1 Themal, Gen Deliv Violations |
N1-ST46, GD-S5, GD-S7, N2-ST69, N2-ST70, N2-ST71 |
Dominion |
640 |
Increase the maximum operating temperature of 230 kV line 227 |
800 |
Reconductor 230 kV Line 227 between Pleasant View Junction and Beaumeade |
418 |
Rebuild 230 kV Line 227 Cochran Mill DP - Pleasant View Junction and reconductor Pleasant View Junction - Beaumeade and Cochran Mill DP - Belmont |
Summer & Winter Generation Deliverablity |
GD-S537, GD-S538, GD-W441, GD-W442 |
DPL |
626 |
Install a series reactor on the Silverside-Darley 69 kV line |
820 |
Install a SmartWire device in series with the Silverside-Darley 69 kV line |
673 |
Reconductor Silverside-Darley and Darley-Naamans 69 kV lines and upgrade terminal equipment |
174 |
Build a new 69 kV line Edge Moor-Claymont |
36 |
Build a new substation near Linwood Substation (PECO), build a in 230 kV line to Edge Moor and tap the Chichester-Linwood 230 kV Line (PECO). |
522 |
Build new 230 kV line Edge Moor-Chichester |
637 |
Build new substation near Linwood Substation (PECO), build a new 230 kV line to Harmony, and tap the Chichester-Linwood 230 kV Line (PECO). |
839 |
Build a new 230 kV line Harmony-Chichester |
Summer & Winter N-1-1 Voltage Violations |
N2-SVM1, N2-SVM2, N2-SVM3, N2-SVM4, N2-SVM5, N2-SVM6, N2-SVM7, N2-SVM8, N2-SVM9, N2-SVM10, N2-SVM11, N2-SVM12, N2-SVM13, N2-WVM1, N2-WVM2, N2-WVM3, N2-WVM4, N2-WVM5, N2-WVM6, N2-WVD1, N2-WVD2, N2-WVD3, N2-WVD4, N2-WVD5, N2-WVD6, N2-WVD7, N2-WVD8, N2-WVD9, N2-WVD10 |
APS |
702 |
Reconfigure Stonewall 138 kV substation to a six-breaker breaker-and-a-half layout and install two (2) 36 MVAR capacitors |
620 |
Reconfigure Hampshire 138 kV switching station to a networked ring bus. Install one (1) 34.6 MVAR capacitor at Inwood |
788 |
Build a new 500/138 kV station (Woodside) tapping Doubs-Bismark 500 kV, Stonewall-Feagan’s Mill 138 kV and Stonewall-Inwood 138 kV lines |